Sponsored by DensDeck® Prime Roof Board, this module examines the fire safety challenges associated with photovoltaic installations on commercial flat roofs, exploring the requirements of Approved Document B, the limitations of conventional fire testing and the role of roof assembly specification in managing risks beyond minimum regulatory compliance
Deadline for completion: Friday 1 January 2027

The role of the commercial flat roof is changing. Once primarily responsible for protecting a building from the elements, roofs are increasingly accommodating renewable energy systems, building services equipment and other installations that place additional demands on their performance.
Among these developments, solar photovoltaic (PV) systems present particular challenges for designers and specifiers. While rooftop solar can help building owners reduce reliance on grid electricity, introducing electrical equipment also changes the risks that the roof assembly must accommodate.
These extend beyond the additional weight of panels and supporting equipment. Electrical faults can create potential ignition sources, while the presence of panels can influence how a fire develops and spreads. Maintenance access, concentrated loading and damage to waterproofing membranes must also be considered.
In England, Requirement B4(2) of the Building Regulations 2010 addresses the resistance of roofs to external fire spread. However, demonstrating compliance does not necessarily establish how a roof assembly will perform with photovoltaic equipment installed above it.
This raises an important question: how should specifiers approach risks that are not fully represented by conventional roof fire classifications?
Answering it requires an understanding of statutory requirements, industry guidance, insurance considerations and the role of individual components within the wider roof assembly.
Fire safety is one of several performance considerations that must be addressed when specifying a commercial flat roof. In England, the principal statutory requirements are set out in Schedule 1, Part B of the Building Regulations 2010, with supporting guidance provided in Approved Document B.
Requirement B4 concerns external fire spread. B4(1) addresses external walls, while B4(2) requires roofs to adequately resist fire spread over their surfaces and between buildings, having regard to the building’s use and position.
This distinction matters because roofs and external walls are subject to different approaches to fire performance. Restrictions on combustible materials apply to external walls and specified attachments on certain buildings, while roofs are principally assessed for external fire spread under B4(2). Other requirements, including those concerning internal fire spread and compartmentation, may also be relevant.
Approved Document B provides statutory guidance rather than legislation itself. Following its recommendations is one recognised means of demonstrating compliance, but alternative approaches may be appropriate where supported by sufficient evidence.
For commercial buildings, the relevant guidance is principally contained in Approved Document B, Volume 2, which covers buildings other than dwellings.

In England, Requirement B4(2) of the Building Regulations 2010 addresses the resistance of roofs to external fire spread
How is external roof fire performance assessed?
Approved Document B refers to the European classification system for the external fire performance of roofs, established under BS EN 13501-5.
In England, the relevant classification uses test method 4, identified by the suffix (t4), based on testing in accordance with CEN/TS 1187.
Roof constructions are classified from BRoof(t4), representing the highest performance within this classification system, through to FRoof(t4), the lowest. The classifications concern the behaviour of a roof construction under specified external fire exposure conditions, including flame spread and fire penetration.
Importantly, a classification applies to the roof construction covered by the supporting evidence, rather than automatically to each material within it. The waterproofing membrane, insulation, substrate and arrangement of layers can all influence the assembly’s performance.
It is also necessary to distinguish three aspects of fire performance:
These classifications are not interchangeable. A roof assembly achieving BRoof(t4) may incorporate materials with different reaction-to-fire classifications, while an individual product achieving class A1 does not automatically confer a BRoof(t4) classification on the complete roof.
This distinction becomes particularly relevant when additional equipment is introduced above the roof covering.
Approved Document B has undergone amendments, including changes to fire classification references in March 2025 and further amendments effective from September 2026.
A separate government consultation published in 2026 proposed updated guidance for roofs incorporating photovoltaic panels. Those proposals should not be treated as requirements already in force.
Building-applied photovoltaic systems are generally mounted above an existing roof covering, unlike building-integrated systems that form part of the building envelope.
Commercial installations may comprise multiple arrays of panels, mounting structures, direct current cabling, connectors, isolators and inverters. Their introduction changes the conditions under which the roof must perform.
Electrical faults and ignition sources
One potential cause of fire is electrical arcing, which occurs when current passes through a gap between conductors. This can result from damaged cables, deteriorating connections or installation defects.
Photovoltaic systems generate direct current, which can sustain an electrical arc under certain conditions. The resulting heat may ignite nearby combustible materials, including components of the photovoltaic installation or roof covering.
Although fires involving photovoltaic installations are relatively uncommon, poor design, installation or maintenance can increase the likelihood of faults. The risk must therefore be considered across the installation’s intended service life.

Where conventional regulatory guidance does not address every aspect of an installation, specifiers may need to consider additional technical information
Fire development and the limitations of conventional testing
Where a fire occurs beneath photovoltaic panels, the arrangement of the installation can influence how it develops.
The space between panels and the waterproofing membrane may affect heat accumulation, ventilation and flame spread, while the modules and associated components can contribute additional combustible material.
Panels may also restrict firefighting access, obscure the location of a fire and make it more difficult to apply water directly to burning materials beneath them.
These factors are relevant because conventional external roof fire testing does not necessarily reproduce the conditions created by photovoltaic installations.
The BRoof(t4) classification assesses a roof construction under specified external fire exposure conditions. It does not automatically establish how that construction will perform when exposed to an electrical fault beneath photovoltaic panels or account for the influence of panel geometry and mounting equipment.
Research commissioned by the government has examined these issues, including the effects of photovoltaic systems on fire dynamics and firefighting operations. The findings have informed consideration of potential changes to regulatory guidance, although the research itself does not constitute government policy.
Consequently, specifiers must understand the scope of available test evidence and consider whether further assessment is necessary for the proposed installation.
Where conventional regulatory guidance does not address every aspect of an installation, specifiers may need to consider additional technical information.
For commercial photovoltaic roofs, this can include recommendations from industry bodies, insurers and organisations involved in the testing and certification of roofing systems.
Such guidance does not replace the Building Regulations. Instead, it can inform decisions about risks extending beyond the minimum statutory requirements.
The role of RISCAuthority RC62
One relevant publication is RISCAuthority’s RC62: Recommendations for fire safety with photovoltaic panel installations.
The guidance focuses principally on commercial and industrial rooftop photovoltaic systems, addressing fire prevention and mitigation throughout planning, procurement, design, installation, operation and maintenance.
It covers considerations such as electrical system design, panel positioning, compartmentation, access for firefighters and ongoing inspection.
Of particular relevance to roof specification are recommendations concerning the positioning of photovoltaic arrays in relation to compartment walls, the routing of electrical cables and the potential for fire to spread across roof surfaces.
RC62 recommends separation between arrays on either side of compartment walls, with the appropriate arrangement depending on the assessed risk. These recommendations should be considered alongside the building’s fire strategy rather than applied without reference to the particular construction.
Insurance requirements and third-party testing
Commercial property insurers may establish requirements beyond those contained in building regulations, reflecting the potential financial consequences of fire, including damage to buildings, equipment and business operations.
FM Approvals, for example, evaluates roofing assemblies against defined performance criteria, including fire exposure and wind uplift. Its RoofNav database identifies assemblies that have achieved relevant approvals.
Crucially, approval applies to the specific construction and conditions covered by the listing, rather than individual products in isolation. Changing components or installation methods may affect whether an approval remains applicable.
Where insurer approval is required, specifiers should verify that the proposed roof construction corresponds to the relevant approved assembly.

Designers should be able to explain the basis for selecting a roof assembly, identify the supporting performance evidence and establish whether specialist assessment is necessary
Professional responsibility and building safety
The Building Safety Act 2022 introduced changes to the building safety framework in England, alongside subsequent regulations establishing duties relating to competence, co-operation and compliance. These duties do not create a blanket requirement to follow insurer guidance. However, the wider emphasis on accountability reinforces the importance of informed specification decisions.
Designers should be able to explain the basis for selecting a roof assembly, identify the supporting performance evidence and establish whether specialist assessment is necessary. This is particularly important where an existing roof is being refurbished or repurposed to accommodate photovoltaic equipment.
The additional demands associated with photovoltaic installations bring attention to components of the roof assembly that may otherwise receive relatively little consideration during specification.
Among these are roof boards and cover boards, which serve different functions depending on their position within the construction.
In a typical warm flat roof, the structural deck supports an air and vapour control layer, thermal insulation and an external waterproofing system. Additional boards may be incorporated to address particular performance requirements.
A roof board is generally positioned above the structural deck and beneath the insulation. A cover board, by contrast, is installed above the insulation and immediately beneath the waterproofing membrane.
These positions influence how each board contributes to the assembly. A board installed above the structural deck may provide a substrate or contribute to particular fire performance requirements, while a cover board can provide a supporting layer beneath the waterproofing, helping distribute applied loads and limit localised deformation.
Fire performance and material selection
Cover boards can be manufactured from several materials, including gypsum-based products.
Gypsum contains chemically bound water within its crystalline structure. When exposed to sufficient heat, it undergoes calcination, during which some of this water is released as vapour. This process absorbs thermal energy and can delay temperature rise through the material.
However, the presence of gypsum does not automatically establish the reaction-to-fire classification or fire resistance performance of a finished board. These properties depend on the complete product, including facings, additives and coatings, and must be established through appropriate testing.
For example, a board achieving class A1 under BS EN 13501-1 can be described as non-combustible within the scope of that classification.
Where a cover board is installed beneath a waterproofing membrane, its characteristics may influence how heat is transferred to underlying insulation during a fire. Nevertheless, the performance of the complete assembly depends on the interaction between the waterproofing, board, insulation, fixings and structural deck.
Specifiers should therefore avoid assuming that adding a particular board automatically confers a defined fire classification on the roof.
The importance of compartmentation
The relationship between roof construction and fire compartmentation also requires attention.
Compartmentation divides a building into fire-resisting spaces intended to restrict the spread of fire and smoke. Where a compartment wall meets a roof, the junction must be designed to maintain the required fire separation.
Approved Document B, Volume 2, provides guidance on these junctions, including measures intended to limit fire spread across compartment boundaries.
The arrangement of roof layers can influence whether fire could pass between compartments, particularly where combustible insulation or other materials extend across a compartment wall.
The addition of photovoltaic equipment introduces further considerations where panels, cables or mounting systems cross compartment boundaries.
Government-commissioned research has also examined the performance of compartment wall and roof junctions in different roof constructions, reinforcing the importance of assessing the junction as a complete detail.
This may require co-ordination between the architect, fire engineer, roofing specialist and photovoltaic designer.
Mechanical performance and roof resilience
Beyond fire performance, photovoltaic installations introduce additional loading and maintenance demands.
Panels, mounting systems and associated equipment impose permanent loads, which may be distributed across the roof or concentrated at individual support points. Ballasted systems introduce additional weight to resist wind uplift, while mechanically attached systems transfer forces through fixings to the supporting structure.
These loads must be assessed in relation to the structural deck and underlying insulation. Where loads are concentrated, localised compression may occur, potentially affecting the waterproofing membrane.
Cover boards can provide a supporting layer above the insulation, helping distribute some applied loads depending on their mechanical properties and the roof construction. They may also help limit localised deformation caused by foot traffic or maintenance activities.
However, their inclusion does not remove the need to assess structural capacity, insulation performance or photovoltaic mounting arrangements.
Wind uplift is another consideration. Panels can alter aerodynamic conditions above the roof, while mounting systems introduce forces that must be transferred through the supporting construction.
The resistance of the complete assembly must therefore be established through appropriate calculations and supporting evidence, rather than relying on the characteristics of individual components.
The same principle applies to waterproofing. Compatibility between the membrane, cover board, insulation and attachment methods is essential, particularly where photovoltaic panels may restrict future inspection and repair.
These considerations demonstrate why cover boards should be assessed in relation to the complete roof assembly and the demands of the proposed installation.

Source: DensDeck
DensDeck cover and substrate board
The refurbishment of Caterpillar’s facility in Desford, Leicestershire, demonstrates how photovoltaic requirements, operational continuity and insurance considerations can influence roof specification.
The project involved approximately 40,000m² of flat roofing at a facility used for worldwide materials distribution. The building needed to remain operational throughout the 2011 refurbishment, placing constraints on the construction programme.
The existing roof incorporated a bitumen waterproofing membrane and mineral wool insulation. Water ingress had affected its performance, creating potential risks to the building’s operations and contents.
Alongside addressing these defects, the refurbishment aimed to improve thermal performance and accommodate the planned installation of thin-film photovoltaic technology.
The works were undertaken over approximately three months, with the roof divided into smaller working zones to minimise disruption.
Existing layers were removed back to the steel deck before a new air and vapour control layer and polyisocyanurate (PIR) insulation were installed.
DensDeck Roof Boards, supplied by Georgia-Pacific, were positioned above the insulation, providing a supporting substrate beneath an ethylene propylene diene monomer (EPDM) waterproofing membrane.
The cover board formed part of a roof construction designed to accommodate the proposed photovoltaic installation while meeting the project’s operational requirements.
Insurance was another important consideration. Caterpillar’s existing relationship with FM Global meant that FM approval was a key requirement for the roof assembly.
The project illustrates the importance of considering photovoltaic requirements during refurbishment planning rather than treating the installation as a later addition. It also demonstrates how material selection, construction sequencing and insurer requirements must be co-ordinated, particularly where business continuity is essential.
The specification of a commercial photovoltaic roof requires an understanding of how the proposed installation interacts with the underlying construction.
The following questions can help inform the assessment:
Addressing these questions during design can help establish whether the proposed roof assembly is appropriate for its intended use and identify where further specialist assessment may be necessary.
The growing use of commercial rooftops for photovoltaic installations introduces additional considerations for the design, construction and management of flat roofs.
Although the regulatory framework establishes requirements for external fire performance, conventional roof classifications do not necessarily represent every condition associated with photovoltaic equipment. Specifiers must therefore understand the scope of available test evidence and consider where additional assessment is required.
Industry guidance, insurer requirements and third-party certification can help inform these decisions, alongside consideration of the roof assembly’s fire and mechanical performance.
Ultimately, photovoltaic roof specification should be approached as a co-ordinated design exercise involving the roof construction, electrical installation, structural requirements and fire safety strategy. Considering these elements together from the outset provides a clearer basis for material selection and long-term roof management.
Please fill out the form below to complete the module and receive your certificate.
2026-11-18T06:00:00Z
Instead of top-down thinking, councils must be empowered with resources to support grassroots development, argues Ben Derbyshire
2026-11-13T05:00:00Z
Sponsored by ROCKWOOL®, this module examines best-practice fire-stopping, from co‑ordinated specification and system selection through to installation, inspection and record‑keeping
2026-10-30T05:00:00Z
Sponsored by Tobermore, this module explores how facing bricks should be specified as part of a complete wall system, considering durability, structural performance, appearance, movement, sustainability, buildability, procurement and whole-life value, with particular focus on concrete facing bricks in modern construction
2026-10-26T05:00:00Z
Sponsored by George Barnsdale, this module explores how material choice, operational performance, durability, maintenance, repair and end-of-life considerations can influence the whole-life carbon impact of window specification
2026-10-16T05:00:00Z
As flat roofs take on more roles, their design and specification are becoming increasingly complex. This CPD, sponsored by ROCKWOOL®, explores how to assess loading, fire performance, drainage and long-term behaviour as part of a complete roof system
2026-10-09T05:00:00Z
Sponsored by PolyFoam XPS, this CPD module explores the principles behind using extruded polystyrene (XPS) insulation in masonry cavity walls below damp-proof course (DPC) level, examining relevant Building Regulations guidance, detailing approaches and the role of thermal modelling in achieving robust building performance
Site powered by Webvision Cloud